# SS-KPI-09B SS VWAFT (weather-compensated)

> SS VWAFT (weather-compensated): ± 3 °C vs compensated setpoint. Substation KPI, HNTAS · assessed. Monitoring points, threshold and calculation.

| | |
|---|---|
| Element | Substation (SS) |
| Standing | HNTAS · assessed |
| Monitoring points | SS1 · 5 min · tF (heat meter, else sensor); heat meter m³/h; SS · tF (setpoint, else design) |
| Threshold | ± 3 °C vs compensated setpoint |
| Calculation | as 09A |
| Period | Monthly |


## Discuss this KPI

Is the threshold right? Does the calculation match what you compute on your networks? [Comment on SS-KPI-09B](https://github.com/heatweb/HNQAP/issues/new?template=kpi-comment.yml&kpi=SS-KPI-09B&title=SS-KPI-09B%3A%20), or report how it behaves on your data. Comments are public and are read before every revision.