Heatweb BMS-to-MQTT Data Connection Guide

Connecting building management systems to the Heatweb telemetry platform Version 1.0 — September 2026


1. Purpose

This guide tells a BMS or controls engineer how to publish plant data to the Heatweb telemetry platform with the minimum of site-side effort. The design principle throughout:

Connect every point, exactly as it is named today. Heatweb does the mapping.

You do not need to rename points to a Heatweb convention, agree a point schedule in advance, or filter to an approved list. Publish everything the station can see; the platform ingests verbatim, and Heatweb maps the incoming identities to standard heat-network monitoring points (flow/return temperatures, heat meters, pump energy, pressures) for KPI calculation, dashboards and HNTAS-aligned reporting. Unrecognised points are stored, not lost — mapping can happen at any time after connection.

Three connection profiles are supported. Pick the one that matches your platform; each has a one-page instruction section below.

Profile For Effort
A — Native topics Any MQTT-capable controller (incl. Trend IQ5 family), gateways, custom kit One topic per point
B — Batch JSON Tridium Niagara stations (N4 / JACE), and Niagara-based OEM front-ends One JSON message per point list — in production use today
C — Sparkplug B Ignition / industrial estates already standardised on Sparkplug Off-the-shelf modules (on request)

2. The address model

Every reading in the platform lives at a six-level MQTT address:

<schema>/<network>/<node>/<device>/<group>/<key>
Level Meaning Example
schema The operator / portfolio (issued by Heatweb) operatorx
network The heat network / site slug (issued by Heatweb) highstreet
node Element of the network: ec (energy centre), substation or block id ec, block_g
device The plant item boiler_1, chp, hiu, block_g
group The kind of value: sensor, meter, emeter, setpoint, digin, driver sensor
key The point name tF, tR, kwh, speed

Heatweb issues the schema and network values with your credentials. Everything from node down may use your existing naming — lowercase with underscores preferred, no spaces or / in a segment. Broker-side access prefixes ahead of the six levels are tolerated (the address is read right-anchored).

Payloads on native topics are the plain numeric value (72.4). Formatted value strings (72.4 °C {ok} @ def) belong on the batch JSON profile, whose decoder extracts the number; published raw to a native topic they are kept as text values — visible, never dropped, but deliberately excluded from numeric analytics.

3. Broker connection

Host mqtt.heatweb.cloud
Port 8883 (TLS)
Protocol MQTT v3.1.1 or v5
Credentials Issued per site by Heatweb — publish-only permission on your <schema>/#
QoS 0 or 1
Retained messages Not required
Cadence On change-of-value where supported, else a periodic scan. 1–5 minutes suits most heat-network KPIs; faster is accepted.

Nothing on site is polled from outside and no inbound firewall rules are needed: the connection is outbound MQTT/TLS from your station or gateway.

4. Profile A — native topics

For any controller or gateway that can publish MQTT directly (including the Trend IQ5 family — IQ500/IQ528 are natively MQTT-capable; legacy Trend IQ4 should use Profile B via a Niagara/IQVISION layer or a gateway).

  1. Configure the broker connection from §3.
  2. For each point, publish its plain numeric value to its six-level topic, e.g.:
    operatorx/highstreet/ec/boiler_1/sensor/tF        → 71.8
    operatorx/highstreet/ec/dhn/meter/kwh             → 2918920
    operatorx/highstreet/block_g/hiu_riser/sensor/dP  → 0.42
    
  3. Publish on change-of-value with a periodic re-send (heartbeat) so quiet points remain visibly alive.
  4. Tell Heatweb the connection is live. Nothing else is needed — points appear in the platform within seconds and mapping proceeds from there.

5. Profile B — Niagara batch JSON (in production use)

For Tridium Niagara N4 stations and JACE controllers, and the many OEM front-ends built on Niagara. This profile is running in production today, ingesting live energy-centre and per-block substation data exported from a Niagara station on a UK district heating scheme.

Niagara's strength is exporting a whole point list as one JSON message (JSON Toolkit, or the MQTT Service payload builder). Rather than fight that, the platform accepts the batch shape natively:

5.1 Point naming — no renaming required

Exported points are accepted under their existing displayNames, exactly as they are — no renaming, and therefore no impact on the site's own graphics, schedules or histories. A point named AHU2_SupplyTemp ingests verbatim (addressed under its batch, e.g. …/boilers/point/ahu2_supplytemp) and is then mapped platform-side to the standard monitoring point it represents. At portfolio scale this matters: mapping thousands of as-found names is Heatweb's job, done centrally with bulk pattern rules — not a renaming exercise across every station.

Optionally, a site that wants its data pre-organised by plant item can name exported points as <device>__<key>_<group> — the plant item, a double underscore, the point name, and the value kind as the final underscore-separated token. Points named this way resolve straight to structured addresses without any mapping step:

Niagara displayName Resolved address (device/group/key)
boiler_1__flow_temp_sensor boiler_1/sensor/flow_temp
block_g__cummulative_energy_meter block_g/meter/cummulative_energy
AHU2_SupplyTemp (unrenamed) <batch>/point/ahu2_supplytemp — mapped by Heatweb

Both styles can coexist in one batch; where the convention is used, a displayName is a one-field Workbench edit that does not disturb the underlying point or its history.

5.2 Envelope

Publish batches as a JSON object with a status array:

{
  "topic":     "operatorx/highstreet/ec/hm/json/boilers",
  "timestamp": "06-Sep-26 12:58 PM BST",
  "status": [
    { "displayName": "boiler_1__flow_temp_sensor", "value": "71.8 °C {ok} @ def" },
    { "displayName": "boiler_1__return_temp_sensor", "value": "58.2 °C {ok} @ def" },
    { "displayName": "dhn__pump_speed_driver", "value": "42.0 % {ok} @ def" }
  ]
}

Niagara's native value strings — units, {ok}/{down}/{fault} status flags, priority slots — are accepted as-is; the platform extracts the numeric value and does not require you to strip formatting.

5.3 Publish topic

Publish each batch to:

<schema>/<network>/<node>/<station>/json/<batchName>

The literal json at level five is what routes the message to the batch decoder. <batchName> is free (e.g. boilers, block_g, dhn); one batch per plant area keeps messages a comfortable size. Group points under the node they belong to (ec for energy-centre plant; a block/substation id for consumer-side points).

5.4 Station-side steps (Workbench)

  1. Add the MQTT connection (§3) using the Niagara MQTT driver or MQTT Service.
  2. Build the point list(s) for export — all points; do not filter.
  3. Optionally apply the naming convention (§5.1) — or skip this step entirely and leave every displayName as-is.
  4. Encode the list to JSON (JSON Toolkit pointsToJson or the MQTT Service payload builder) and link the output string to the publish topic (§5.3).
  5. Trigger on a 1–5 minute interval (or change-of-value where preferred).

5.5 What happens platform-side

Each batch is exploded into per-point readings at full six-level addresses, typed (numeric analytics never polluted by text values), stored in a compressed time-series store with two-year retention, and surfaced in the Heatweb App within seconds — per-device activity, latest values, and history. Heatweb then maps point identities to the standard heat-network monitoring points for KPIs and reporting; unmapped points remain stored and queryable throughout.

6. Profile C — Sparkplug B

For estates already standardised on MQTT Sparkplug B (typically Ignition with the Cirrus Link modules), Sparkplug metric batches can be accepted — the industrial-standard equivalent of Profile B. The decoding is provisioned per project rather than enabled on request: the site-side effort is configuration of an off-the-shelf module, and the platform side is agreed at the outset. Talk to us before assuming this profile.

7. Data quality, security and governance

8. Connection checklist

  1. Request credentials from Heatweb → receive schema, network, username, password.
  2. Pick your profile (A: native topics · B: Niagara batch JSON · C: Sparkplug B).
  3. Configure the broker connection (§3) and publish all points.
  4. Confirm with Heatweb — arrival is verified live and mapping begins.

Heatweb Solutions Ltd — heat network telemetry, analysis and optimisation.