Monitoring points

Every monitoring point that heat network technical assurance asks for, with the address it is published under in HNQAP-MQTT v1. 106 entries, generated 2026-10-25. Download as monitoring-points.json.

A full address is {schema}/{network}/{element}/ followed by the device, vargroup and varkey shown. On a monitored element the device is named for the point it serves (intake, offtake, boundary and so on, see protocol §2.2), so a receiver finds each point without a mapping step:

acme/riverside_court/ss1/intake/hmeter/kwh

Point codes and descriptions paraphrase the scheme drafts; the scheme documents remain the authority. Some of these names, including the hmeter and meter vargroups, are in use on live networks but not yet in the vocabulary export. They are being registered, and this table is their reference until then. Comments on any address are welcome as issues.

Energy Centre (EC)

Live readings

Point Monitoring point Quantity Address (device/vargroup/varkey) Units Minimum frequency
EC5 Make-up Water meter Accumulated Volume makeup/meter/m3 m³ 30 min
EC8 Operating pressure measurement point Static Pressure pressure/sensor/pSystem bar 5 min
EC7 Distribution differential pressure measurement point Differential Pressure EC7/sensor/dpSupply kPa 5 min
EC4 Distribution pump set Accumulated Energy pump/emeter/kwhElectric kWh 30 min
EC3 Energy Centre boundary Accumulated Energy boundary/hmeter/kwh kWh 5 min
EC3 Energy Centre boundary Accumulated Volume boundary/hmeter/m3 m³ 5 min
EC3 Energy Centre boundary Flow Temperature boundary/hmeter/tF °C 5 min
EC3 Energy Centre boundary Instantaneous Flow Rate boundary/hmeter/m3h m³/h 5 min
EC3 Energy Centre boundary Instantaneous Power boundary/hmeter/kw kW 5 min
EC3 Energy Centre boundary Return Temperature boundary/hmeter/tR °C 5 min
EC6 Index differential pressure measurement point Differential Pressure EC6/sensor/dpIndex kPa 5 min
EC2 Heat Source energy output Accumulated Energy EC2/hmeter/kwh kWh 5 min
EC2 Heat Source energy output Accumulated Volume EC2/hmeter/m3 m³ 5 min
EC2 Heat Source energy output Flow Temperature EC2/hmeter/tF °C 5 min
EC2 Heat Source energy output Instantaneous Flow Rate EC2/hmeter/m3h m³/h 5 min
EC2 Heat Source energy output Instantaneous Power EC2/hmeter/kw kW 5 min
EC2 Heat Source energy output Return Temperature EC2/hmeter/tR °C 5 min
EC1 Heat source energy input Accumulated Energy EC1/meter/kwh kWh 30 min
EC1 Heat source energy input Accumulated Volume of Gas EC1/meter/m3Gas m³ 30 min

Values entered once (design, identity)

Value Address Units
HNTAS element code — instance ID assigned at registration (e.g. 00005) system/elementCode
Parent element — energy flows from here (e.g. cd1 / cd1) system/parentElement
System Volume design/systemVolume litres
Maximum System Pressure design/maxPressure bar
Maximum Supply DP design/maxDPSupply kPa
Design Annual Pump Energy Use design/kwhAnnualPump kWh
Design flow temperature design/tF °C
Minimum Flow Temperature design/minFlowTemp °C
Minimum Index Differential Pressure design/minDPIndex kPa
Minimum Generation Efficiency design/efficiency %
DESNZ fuel type ID (carbon calculator Table 1: 17 mains gas, 25 natural gas, 28 electricity, 27 biomass, 15 hydrogen) design/fuelType ID
Declared boiler efficiency (fraction or %) - carbon fuel-input fallback when generation is unmetered design/boilerEfficiency fraction
Design heat fraction of the lead heat source design/heatFraction %

Derived by the platform

Value Address Units
Distribution efficiency (delivered / generated) kpi/distributionEfficiency %
Carbon content of delivered heat kpi/carbonContent kgCO2e/kWh

District Distribution (DD)

Live readings

Point Monitoring point Quantity Address (device/vargroup/varkey) Units Minimum frequency
DD3 DP Measuring Point Differential pressure at Index DD3/sensor/dpIndex kPa 5 min
DD1 Intake Boundary Accumulated Energy intake/hmeter/kwh kWh 30 min
DD1 Intake Boundary Accumulated Volume intake/hmeter/m3 m³ 30 min
DD1 Intake Boundary Flow Temperature intake/hmeter/tF °C 30 min
DD1 Intake Boundary Return Temperature intake/hmeter/tR °C 30 min
DD1 Intake Boundary Instantaneous Power intake/hmeter/kw kW 30 min
DD1 Intake Boundary Instantaneous Flow Rate intake/hmeter/m3h m³/h 30 min

Values entered once (design, identity)

Value Address Units
HNTAS element code — instance ID assigned at registration (e.g. 00005) system/elementCode
Parent element — energy flows from here (e.g. cd1 / cd1) system/parentElement
Minimum Index Differential Pressure design/minDPIndex kPa
Expected average flow temperature design/tF °C
Expected average return temperature design/tR °C
Design maximum bypass flowrate design/maxBypassFlow m³/h
Minimum required flow temperature design/minFlowTemp °C
Dwellings served (heat-loss W/dwelling basis) design/dwellings
Non-domestic connected load (heat-loss W/kW basis) design/kwConnection kW

Derived by the platform

Value Address Units
Flow/return ΔT kpi/deltaT K

Substation (SS)

Live readings

Point Monitoring point Quantity Address (device/vargroup/varkey) Units Minimum frequency
SS6 Defined differential pressure exceedance measurement point Differential Pressure SS6/sensor/dpOff kPa 5 min
SS5 Defined index differential pressure measurement point Differential Pressure SS5/sensor/dpIndex kPa 5 min
SS7 Defined operating pressure measurement point Static Pressure pressure/sensor/pOff bar 5 min
SS1 Intake Boundary Accumulated Energy intake/hmeter/kwh kWh 5 min
SS1 Intake Boundary Accumulated Volume intake/hmeter/m3 m³ 5 min
SS1 Intake Boundary Flow Temperature intake/hmeter/tF °C 5 min
SS1 Intake Boundary Instantaneous Flow Rate intake/hmeter/m3h m³/h 5 min
SS1 Intake Boundary Instantaneous Power intake/hmeter/kw kW 5 min
SS1 Intake Boundary Return Temperature intake/hmeter/tR °C 5 min
SS3 Network distribution pump Accumulated Energy pump/emeter/kwhElectric kWh 30 min
SS2 Offtake Boundary Accumulated Energy offtake/hmeter/kwhOff kWh 5 min
SS2 Offtake Boundary Accumulated Volume offtake/hmeter/m3Off m³ 5 min
SS2 Offtake Boundary Flow Temperature offtake/hmeter/tFOff °C 5 min
SS2 Offtake Boundary Instantaneous Flow Rate offtake/hmeter/m3hOff m³/h 5 min
SS2 Offtake Boundary Instantaneous Power offtake/hmeter/kwOff kW 5 min
SS2 Offtake Boundary Return Temperature offtake/hmeter/tROff °C 5 min
SS4 Water meter Accumulated Volume watermeter/meter/m3 m³ 30 min

Values entered once (design, identity)

Value Address Units
HNTAS element code — instance ID assigned at registration (e.g. 00005) system/elementCode
Parent element — energy flows from here (e.g. cd1 / cd1) system/parentElement
Maximum Supply DP design/maxDPOff kPa
Minimum Index Differential Pressure design/minDPIndex kPa
Maximum System Pressure design/maxPressure bar
Design Annual Pump Energy Use design/kwhAnnualPump kWh
Maximum PHE Approach Temperature design/maxApproachTemp °C
Minimum Output Temperature design/minFlowTempOff °C
Design flow temperature (secondary) design/tFOff °C
System Volume design/systemVolume litres

Communal Distribution (CD)

Live readings

Point Monitoring point Quantity Address (device/vargroup/varkey) Units Minimum frequency
CD3 DP Measuring Point Differential pressure at Index CD3/sensor/dpIndex kPa 5 min
CD1 Intake Boundary Accumulated Energy intake/hmeter/kwh kWh 30 min
CD1 Intake Boundary Accumulated Volume intake/hmeter/m3 m³ 30 min
CD1 Intake Boundary Flow Temperature intake/hmeter/tF °C 30 min
CD1 Intake Boundary Instantaneous Flow Rate intake/hmeter/m3h m³/h 30 min
CD1 Intake Boundary Instantaneous Power intake/hmeter/kw kW 30 min
CD1 Intake Boundary Return Temperature intake/hmeter/tR °C 30 min

Values entered once (design, identity)

Value Address Units
HNTAS element code — instance ID assigned at registration (e.g. 00005) system/elementCode
Parent element — energy flows from here (e.g. cd1 / cd1) system/parentElement
Minimum Index Differential Pressure design/minDPIndex kPa
Expected average flow temperature design/tF °C
Expected average return temperature design/tR °C
Dwellings served (heat-loss W/dwelling basis) design/dwellings
Non-domestic connected load (heat-loss W/kW basis) design/kwConnection kW
Design maximum bypass flowrate design/maxBypassFlow m³/h
Minimum flow temperature design/minFlowTemp °C

Derived by the platform

Value Address Units
Accumulated Energy calculated/kwh kWh
Accumulated Volume calculated/m3 m³

Consumer Connection (CC)

Live readings

Point Monitoring point Quantity Address (device/vargroup/varkey) Units Minimum frequency
CC1 Consumer Connection Boundary Accumulated Energy boundary/hmeter/kwh kWh 30 min
CC1 Consumer Connection Boundary Accumulated Volume boundary/hmeter/m3 m³ 30 min
CC1 Consumer Connection Boundary Flow Temperature boundary/hmeter/tF °C 30 min
CC1 Consumer Connection Boundary Instantaneous Flow Rate boundary/hmeter/m3h m³/h 30 min
CC1 Consumer Connection Boundary Instantaneous Power boundary/hmeter/kw kW 30 min
CC1 Consumer Connection Boundary Return Temperature boundary/hmeter/tR °C 30 min

Values entered once (design, identity)

Value Address Units
HNTAS element code — instance ID assigned at registration (e.g. 00005) system/elementCode
Parent element — energy flows from here (e.g. cd1 / cd1) system/parentElement
HNTAS metering point ID system/hntasMPID

Derived by the platform

Value Address Units
Flow/return ΔT kpi/deltaT K