CC-KPI-08 Consumer Connection volume-weighted average temperature difference (VWATD)

Element Consumer Connection (CC)
Standing HNTAS · assessed
Monitoring points CC1 · 30 min · heat meter kWh, m³
Threshold ≥ 5 °C (pair: CC-07 or CC-08 must be met)
Calculation kWh register delta ÷ (1.163 · m³ register delta)
Period Monthly

Discuss this KPI

Is the threshold right? Does the calculation match what you compute on your networks? Comment on CC-KPI-08, or report how it behaves on your data. Comments are public and are read before every revision.

Machine-readable

This KPI is a row of kpi-reference.json (element CC, code CC-KPI-08). The notation and rules that apply to every KPI are on the reference page.