HNQAP

SS-KPI-09B SS VWAFT (weather-compensated)

Element Substation (SS)
Standing HNTAS · assessed
Monitoring points SS1 · 5 min · tF (heat meter, else sensor); heat meter m³/h; SS · tF (setpoint, else design)
Threshold ± 3 °C vs compensated setpoint
Calculation as 09A
Period Monthly

Discuss this KPI

Is the threshold right? Does the calculation match what you compute on your networks? Comment on SS-KPI-09B, or report how it behaves on your data. Comments are public and are read before every revision.

Machine-readable

This KPI is a row of kpi-reference.json (element SS, code SS-KPI-09B). The notation and rules that apply to every KPI are on the reference page.