HNQAP

CC-KPI-C-07 Consumer Connection cooling volume-weighted average return temperature

Element Consumer Connection (CC)
Standing HNTAS-style · proposed
Monitoring points CC1 · 30 min · cooling meter tR, m³/h
Threshold ≥ design cooling return − 2 °C (proposed; pair: C-07 or C-08 must be met)
Calculation Σ(tR · q) ÷ Σ q over 5-minute buckets. Uses design/tRCool (proposed)
Period Monthly

Part of the Cooling forms family.

Discuss this KPI

Is the threshold right? Does the calculation match what you compute on your networks? Comment on CC-KPI-C-07, or report how it behaves on your data. Comments are public and are read before every revision.

Machine-readable

This KPI is a row of kpi-reference.json (element CC, code CC-KPI-C-07). The notation and rules that apply to every KPI are on the reference page.