HNQAP

CC-KPI-C-08 Consumer Connection cooling volume-weighted average temperature difference

Element Consumer Connection (CC)
Standing HNTAS-style
Monitoring points CC1 · 30 min · cooling meter kWh, m³
Threshold ≥ 4 °C (proposed; pair: C-07 or C-08 must be met)
Calculation ΔT = ΔE ÷ (1.163 · ΔV); ΔE, ΔV = register deltas over the period (kWh, m³)
Period Monthly

Part of the Cooling forms family.

Discuss this KPI

Is the threshold right? Does the calculation match what you compute on your networks? Comment on CC-KPI-C-08, or report how it behaves on your data. Comments are public and are read before every revision.

Machine-readable

This KPI is a row of kpi-reference.json (element CC, code CC-KPI-C-08). The notation and rules that apply to every KPI are on the reference page.