HNQAP

EC-KPI-04 Energy Centre unplanned interruptions

Element Energy Centre (EC)
Standing HNTAS · assessed
Monitoring points EC · tF (sensor, else heat meter); sensor dP
Threshold ≤ 3 a year
Calculation count of >12h periods below min flow temp OR min dP without 48h notice. Uses design/minFlowTemp design/minDPIndex
Period Previous 12 months

Discuss this KPI

Is the threshold right? Does the calculation match what you compute on your networks? Comment on EC-KPI-04, or report how it behaves on your data. Comments are public and are read before every revision.

Machine-readable

This KPI is a row of kpi-reference.json (element EC, code EC-KPI-04). The notation and rules that apply to every KPI are on the reference page.