CC-KPI-M-06 Flow comes to rest (no constant flow)

Element Consumer Connection (CC)
Standing Heatweb
Monitoring points CC1 · 30 min · heat meter m³/h; cooling meter m³/h
Threshold ≥ 2% of flow readings at zero
Calculation readings with q = 0 ÷ all q readings, per meter (needs ≥ 6 readings); below target = flow never at rest: bypass or control fault
Period Rolling 7 days; month

Part of the Meter health family.

Discuss this KPI

Is the threshold right? Does the calculation match what you compute on your networks? Comment on CC-KPI-M-06, or report how it behaves on your data. Comments are public and are read before every revision.

Machine-readable

This KPI is a row of kpi-reference.json (element CC, code CC-KPI-M-06). The notation and rules that apply to every KPI are on the reference page.