#CC-KPI-M-07 No low temperature difference at volume
| Element | Consumer Connection (CC) |
| Standing | Heatweb |
| Monitoring points | CC1 · 30 min · heat meter kWh, m³; cooling meter kWh, m³ |
| Threshold | heat: not (ΔT < 5 °C and > 150 L/day); cooling: not (ΔT < 2 °C and > 1,000 L/day) |
| Calculation | ΔT = ΔE ÷ (1.163 · ΔV); L/day = 1000 · ΔV ÷ days |
| Period | Rolling 7 days; month |
Part of the Meter health family.
#Discuss this KPI
Is the threshold right? Does the calculation match what you compute on your networks? Comment on CC-KPI-M-07, or report how it behaves on your data. Comments are public and are read before every revision.
#Machine-readable
This KPI is a row of kpi-reference.json (element CC, code CC-KPI-M-07). The notation and rules that apply to every KPI are on the reference page.
#Related KPIs on the consumer connection
- CC-KPI-M-01 Meter reporting (not silent)
- CC-KPI-M-02 Meter channel coverage
- CC-KPI-M-03 Meter reading cadence
- CC-KPI-M-04 Register integrity
- CC-KPI-M-05 Plausible temperature difference
- CC-KPI-M-06 Flow comes to rest (no constant flow)
- CC-KPI-M-08 No simultaneous heating and cooling
- CC-KPI-M-09 Load follows demand (no flat load)