HNQAP

CC-KPI-M-07 No low temperature difference at volume

Element Consumer Connection (CC)
Standing Heatweb
Monitoring points CC1 · 30 min · heat meter kWh, m³; cooling meter kWh, m³
Threshold heat: not (ΔT < 5 °C and > 150 L/day); cooling: not (ΔT < 2 °C and > 1,000 L/day)
Calculation ΔT = ΔE ÷ (1.163 · ΔV); L/day = 1000 · ΔV ÷ days
Period Rolling 7 days; month

Part of the Meter health family.

Discuss this KPI

Is the threshold right? Does the calculation match what you compute on your networks? Comment on CC-KPI-M-07, or report how it behaves on your data. Comments are public and are read before every revision.

Machine-readable

This KPI is a row of kpi-reference.json (element CC, code CC-KPI-M-07). The notation and rules that apply to every KPI are on the reference page.