HNQAP

CC-KPI-M-08 No simultaneous heating and cooling

Element Consumer Connection (CC)
Standing Heatweb
Monitoring points CC1 · 30 min · heat meter kWh; cooling meter kWh
Threshold < 30% of active days
Calculation days with heat ΔE > 0.5 kWh and cooling ΔE > 0.5 kWh ÷ days with either
Period Rolling 7 days; month

Part of the Meter health family.

Discuss this KPI

Is the threshold right? Does the calculation match what you compute on your networks? Comment on CC-KPI-M-08, or report how it behaves on your data. Comments are public and are read before every revision.

Machine-readable

This KPI is a row of kpi-reference.json (element CC, code CC-KPI-M-08). The notation and rules that apply to every KPI are on the reference page.